Grounding
Earthing Transformers
Grounding
Earthing Transformers
Earthing transformers form an artificial neutral on systems that lack one.
- Zig-zag or star-delta forms
- Short-time fault rating
- For ungrounded or delta systems
An earthing transformer is rated by fault current and time rather than continuous kVA. Define the neutral current, duration and any auxiliary load winding.
They suit delta-fed solar and industrial networks.
Neutral grounding transformer and zig-zag design
An earthing transformer is also called a neutral grounding transformer. The usual design is a zig-zag (ZN) winding, which gives a low impedance path for earth-fault current while carrying almost no current in normal service. It is rated for the earth-fault current and its duration from the protection study, rather than for a continuous kVA. Some designs add an LV winding (ZNyn11) for auxiliary supply.
Engineering references
Specify the vector group in your enquiry; see transformer vector groups explained (Dyn11, Dyn1, YNyn0).
Specify an earthing transformer
Give fault current and duration. Email info@jaybeeindustries.com.