Off-circuit tap changers: how to choose and set the right tap

Most distribution transformers have an off-circuit tap changer that is set once and forgotten. Setting it correctly can noticeably improve the voltage your plant sees.

Posted on

Almost every distribution transformer has a tap changer, a switch that changes the number of turns in the HV winding to adjust the output voltage. On distribution transformers, this is usually an off-circuit tap changer (OCTC), which can only be operated when the transformer is de-energised. It is commonly set during commissioning and often never touched again, even when the supply voltage at the site is consistently high or low. Understanding how to use it can improve voltage at your equipment.

Tap changers and parallel transformers

Where two or more transformers operate in parallel, their tap positions must correspond so that their output voltages match. A mismatch causes circulating current between the units, adding losses and heating even when the external load is light. When changing taps on parallel transformers, change all of them together, record the positions, and check currents after re-energising.

What the taps do

The tap changer offers several positions around the nominal ratio, typically in steps of a few percent. Selecting a different tap changes the turns ratio:

  • If incoming HV voltage is consistently higher than nominal, selecting a tap that adds HV turns reduces the LV output back towards nominal.
  • If incoming HV voltage is consistently lower, selecting a tap that removes HV turns raises the LV output.

The exact tap range and step size are shown on the rating and diagram plate, along with which position corresponds to which voltage. Always refer to your transformer's own plate, since conventions vary.

When to consider changing the tap

Consider reviewing the tap setting if:

  • LV voltage at the transformer is consistently high or low at typical load.
  • Equipment shows undervoltage or overvoltage alarms.
  • Motors run hot or lighting fails early due to high voltage.
  • The utility has changed the network and supply voltage has shifted.

Gather readings first

Do not change taps on a guess. Record LV voltages at the transformer at different times: light load, typical load and peak load, over several days. If possible, record HV voltage too. Voltage at the transformer is not the same as at the far end of long cables, so also check voltage at critical equipment.

Choosing the position

The goal is to keep voltage within an acceptable band at all load levels. If voltage is high at light load and acceptable at peak, a tap that lowers voltage slightly may help, but check that peak-load voltage does not become too low. Compromise is often required. Where voltage swings are large, an off-circuit tap changer may not be enough, and an on-load tap changer or voltage regulation equipment may need to be considered.

Operating safely

An off-circuit tap changer must only be operated when the transformer is fully de-energised and isolated on both HV and LV sides, with earthing applied as per safety procedures. Operating it under load can cause serious damage and danger. Follow these steps:

  • Obtain proper permits and isolate the transformer.
  • Verify isolation and apply earthing.
  • Unlock the tap changer handle, move it to the new position and ensure it locks fully into position.
  • Record the change in the maintenance log.
  • Remove earths, re-energise and check voltages.

Common mistakes

  • Operating the tap changer while energised.
  • Leaving the handle between positions.
  • Changing taps without recording.
  • Changing taps on transformers in parallel without matching positions, which causes circulating currents.

Maintenance

Off-circuit tap changers that are never moved can develop contact films. During planned maintenance, some engineers exercise the tap changer through its range and return it to the selected position, while de-energised, to keep contacts clean. Follow the manufacturer's guidance.

If you need help interpreting your transformer's plate or readings, contact us. Offers for new transformers are prepared on request; we do not publish prices.

Send your enquiry

Call toll-free 1800 309 9948, message us on WhatsApp at +91 98162 95407, or email info@jaybeeindustries.com. Mention this article and your site location so the right team responds. We reply with technical options; we do not publish prices, and every offer is prepared for your specification.

Related pages on this site

Request a quote Call 1800 309 9948 WhatsApp +91 98162 95407 info@jaybeeindustries.com

← All posts

☎ Call WhatsApp